nidaqmx.system
- class nidaqmx.system.system.System[source]
Bases:
object
Represents a DAQmx system.
Contains static properties that access tasks, scales, and global channels stored in Measurement Automation Explorer (MAX), performs immediate operations on DAQ hardware, and creates classes from which you can get information about the hardware.
- class DriverVersion(major_version, minor_version, update_version)
Bases:
tuple
- property major_version
Alias for field number 0
- property minor_version
Alias for field number 1
- property update_version
Alias for field number 2
- add_cdaq_sync_connection(ports_to_connect)[source]
Adds a cDAQ Sync connection between devices. The connection is not verified.
- Parameters
ports_to_connect (nidaqmx.types.CDAQSyncConnection) – Specifies the cDAQ Sync ports to connect.
- are_configured_cdaq_sync_ports_disconnected(chassis_devices_ports='', timeout=- 1.0)[source]
Verifies configured cDAQ Sync connections between devices. Failures generally indicate a wiring issue or that a device has been powered off or removed. Stop all NI-DAQmx tasks running on the devices prior to running this function because any running tasks cause the verification process to fail.
- Parameters
chassis_devices_ports (Optional[str]) – Specifies the names of the CompactDAQ chassis, C Series modules, or cDAQ Sync ports in comma separated form to search. If no names are specified, all cDAQ Sync ports on connected, non-simulated devices are scanned.
timeout (Optional[float]) – Specifies the time in seconds to wait for the device to respond before timing out.
- Returns
Returns the port-to-port connections that failed verification.
- Return type
- auto_configure_cdaq_sync_connections(chassis_devices_ports='', timeout=- 1.0)[source]
Detects and configures cDAQ Sync connections between devices. Stop all NI-DAQmx tasks running on the devices prior to running this function because any running tasks cause auto-configuration to fail.
- Parameters
chassis_devices_ports (Optional[str]) – Specifies the names of the CompactDAQ chassis, C Series modules, or cDAQ Sync ports in comma separated form to search. If no names are specified, all cDAQ Sync ports on connected, non-simulated devices are scanned.
timeout (Optional[float]) – Specifies the time in seconds to wait for the device to respond before timing out. If a timeout occurs, no configuration is changed.
- Returns
Returns the configured port-to-port connections.
- Return type
- connect_terms(source_terminal, destination_terminal, signal_modifiers=SignalModifiers.DO_NOT_INVERT_POLARITY)[source]
Creates a route between a source and destination terminal. The route can carry a variety of digital signals, such as triggers, clocks, and hardware events.
- Parameters
source_terminal (str) – Specifies the originating terminal of the route. A DAQmx terminal constant lists all terminals available on devices installed in the system. You also can specify a source terminal by specifying a string that contains a terminal name.
destination_terminal (str) – Specifies the receiving terminal of the route. A DAQmx terminal constant provides a list of all terminals available on devices installed in the system. You also can specify a destination terminal by specifying a string that contains a terminal name.
signal_modifiers (Optional[nidaqmx.constants.SignalModifiers]) – Specifies whether to invert the signal this function routes from the source terminal to the destination terminal.
- property devices
Indicates the collection of devices for this DAQmx system.
- Type
nidaqmx.system._collections.DeviceCollection
- disconnect_terms(source_terminal, destination_terminal)[source]
Removes signal routes you created by using the DAQmx Connect Terminals function. The DAQmx Disconnect Terminals function cannot remove task-based routes, such as those you create through timing and triggering configuration.
- Parameters
source_terminal (str) – Specifies the originating terminal of the route. A DAQmx terminal constant lists all terminals available on devices installed in the system. You also can specify a source terminal by specifying a string that contains a terminal name.
destination_terminal (str) – Specifies the receiving terminal of the route. A DAQmx terminal constant provides a list of all terminals available on devices installed in the system. You also can specify a destination terminal by specifying a string that contains a terminal name.
- property driver_version
Indicates the major, minor and update portions of the installed version of NI-DAQmx.
major_version (int): Indicates the major portion of the installed version of NI-DAQmx, such as 7 for version 7.0.
minor_version (int): Indicates the minor portion of the installed version of NI-DAQmx, such as 0 for version 7.0.
update_version (int): Indicates the update portion of the installed version of NI-DAQmx, such as 1 for version 9.0.1.
- Type
collections.namedtuple
- get_analog_power_up_states(device_name)[source]
Gets the power up states for analog physical channels.
- Parameters
device_name (str) – Specifies the name as configured in MAX of the device to which this operation applies.
- Returns
Contains the physical channels and power up states set. Each element of the list contains a physical channel and the power up state set for that physical channel.
physical_channel (str): Specifies the physical channel that was modified.
power_up_state (float): Specifies the power up state set for the physical channel specified with the physical_channel input.
channel_type (
nidaqmx.constants.AOPowerUpOutputBehavior
): Specifies the output type for the physical channel specified with the physical_channel input.
- Return type
power_up_states (List[nidaqmx.types.AOPowerUpState])
- get_analog_power_up_states_with_output_type(physical_channels)[source]
Gets the power up states for analog physical channels.
- Parameters
physical_channels (List[str]) – Indicates the physical channels that were modified.
- Returns
Contains the physical channels and power up states set. Each element of the list contains a physical channel and the power up state set for that physical channel.
physical_channel (str): Specifies the physical channel that was modified.
power_up_state (float): Specifies the power up state set for the physical channel specified with the physical_channel input.
channel_type (
nidaqmx.constants.AOPowerUpOutputBehavior
): Specifies the output type for the physical channel specified with the physical_channel input.
- Return type
power_up_states (List[nidaqmx.types.AOPowerUpState])
- get_digital_logic_family_power_up_state(device_name)[source]
Gets the digital logic family for a device.
- Parameters
device_name (str) – Specifies the name as configured in MAX of the device to which this operation applies.
- Returns
Specifies the logic family to set the device to when it powers up. A logic family corresponds to voltage thresholds that are compatible with a group of voltage standards. Refer to device documentation for information on the logic high and logic low voltages for these logic families.
- Return type
- get_digital_power_up_states(device_name)[source]
Gets the power up states for digital physical lines.
- Parameters
device_name (str) – Specifies the name as configured in MAX of the device to which this operation applies.
- Returns
Contains the physical channels and power up states set. Each element of the list contains a physical channel and the power up state set for that physical channel.
physical_channel (str): Indicates the physical channel that was modified.
power_up_state (
nidaqmx.constants.PowerUpStates
): Indicates the power up state set for the physical channel specified with the physical_channel output.
- Return type
- get_digital_pull_up_pull_down_states(device_name)[source]
Gets the resistor level for lines when they are in tristate logic.
- Parameters
device_name (str) – Specifies the name as configured in MAX of the device to which this operation applies.
- Returns
Contains the physical channels and power up states set. Each element of the list contains a physical channel and the power up state set for that physical channel.
physical_channel (str): Indicates the physical channel that was modified.
power_up_state (
nidaqmx.constants.ResistorState
): Indicates the power up state set for the physical channel specified with the physical_channel output.
- Return type
- property global_channels
Indicates the collection of global channels for this DAQmx system.
- Type
nidaqmx.system._collections.PersistedChannelCollection
- remove_cdaq_sync_connection(ports_to_disconnect)[source]
Removes a cDAQ Sync connection between devices. The connection is not verified.
- Parameters
ports_to_disconnect (nidaqmx.types.CDAQSyncConnection) – Specifies the cDAQ Sync ports to disconnect.
- property scales
Indicates the collection of custom scales for this DAQmx system.
- Type
nidaqmx.system._collections.PersistedScaleCollection
- set_analog_power_up_states(device_name, power_up_states)[source]
Updates power up states for analog physical channels.
- Parameters
device_name (str) – Specifies the name as configured in MAX of the device to which this operation applies.
power_up_states (List[nidaqmx.types.AOPowerUpState]) –
Contains the physical channels and power up states to set. Each element of the list contains a physical channel and the power up state to set for that physical channel.
physical_channel (str): Specifies the physical channel to modify.
power_up_state (float): Specifies the power up state to set for the physical channel specified with the physical_channel input.
channel_type (
nidaqmx.constants.AOPowerUpOutputBehavior
): Specifies the output type for the physical channel specified with the physical_channel input.
- set_analog_power_up_states_with_output_type(power_up_states)[source]
Updates power up states for analog physical channels.
- Parameters
power_up_states (List[nidaqmx.types.AOPowerUpState]) –
Contains the physical channels and power up states to set. Each element of the list contains a physical channel and the power up state to set for that physical channel.
physical_channel (str): Specifies the physical channel to modify.
power_up_state (float): Specifies the power up state to set for the physical channel specified with the physical_channel input.
channel_type (
nidaqmx.constants.AOPowerUpOutputBehavior
): Specifies the output type for the physical channel specified with the physical_channel input.
- set_digital_logic_family_power_up_state(device_name, logic_family)[source]
Sets the digital logic family to use when the device powers up.
- Parameters
device_name (str) – Specifies the name as configured in MAX of the device to which this operation applies.
logic_family (nidaqmx.constants.LogicFamily) – Specifies the logic family set to the device to when it powers up. A logic family corresponds to voltage thresholds that are compatible with a group of voltage standards. Refer to device documentation for information on the logic high and logic low voltages for these logic families.
- set_digital_power_up_states(device_name, power_up_states)[source]
Updates power up states for digital physical channels.
- Parameters
device_name (str) – Specifies the name as configured in MAX of the device to which this operation applies.
power_up_states (List[nidaqmx.types.DOPowerUpState]) –
Contains the physical channels and power up states to set. Each element of the list contains a physical channel and the power up state to set for that physical channel.
physical_channel (str): Specifies the digital line or port to modify. You cannot modify dedicated digital input lines.
power_up_state (
nidaqmx.constants.PowerUpStates
): Specifies the power up state to set for the physical channel specified with the physical_channel input.
- set_digital_pull_up_pull_down_states(device_name, power_up_states)[source]
Sets the resistor level to pull up or pull down for lines when they are in tristate logic.
- Parameters
device_name (str) – Specifies the name as configured in MAX of the device to which this operation applies.
power_up_states (List[nidaqmx.types.DOResistorPowerUpState]) –
Contains the physical channels and power up states to set. Each element of the list contains a physical channel and the power up state to set for that physical channel.
physical_channel (str): Specifies the digital line or port to modify. You cannot modify dedicated digital input lines.
power_up_state (
nidaqmx.constants.ResistorState
): Specifies the power up state to set for the physical channel specified with the physical_channel input.
- property tasks
Indicates the collection of saved tasks for this DAQmx system.
- Type
nidaqmx.system._collections.PersistedTaskCollection
- tristate_output_term(output_terminal)[source]
Sets a terminal to high-impedance state. If you connect an external signal to a terminal on the I/O connector, the terminal must be in high-impedance state. Otherwise, the device could double-drive the terminal and damage the hardware. If you use this function on a terminal in an active route, the function fails and returns an error.
- Parameters